1. Communications Enable/Disable |
DM0000 = 0005 No. of SEND words |
DM0001 = 0001 NODE Number |
DM0002 = 3005 MRC-SRC |
DM0003 = 0004 No. of BYTES being sent |
DM0004 = 0001(Enable) 0000(Disable) |
|
2. Run/Stop |
DM0000 = 0005 No. of SEND words |
DM0001 = 0001 NODE Number |
DM0002 = 3005 MRC-SRC |
DM0003 = 0004 No. of BYTES being sent |
DM0004 = 0100(Run) 0101(stop) |
|
3. Read Status |
DM0000 = 0007 No. of SEND words |
DM0001 = 0001 NODE Number |
DM0002 = 0101 MRC-SRC |
DM0003 = 0012 No. of BYTES being sent |
DM0004 = C000 VARIABLE TYPE +1/2 ADDRESS |
DM0005 = 0100 1/1 ADDRESS + 00 |
DM0006 = 0001 No. of ELEMENTS |
Response |
DM0010 = 0004 No. of RECEIVED words |
DM0011 = 0000 RESPONSE CODE |
DM0012 = **** First 16 Bits |
DM0013 = **** Second 16 Bits |
|
4. Read Process Value |
DM0000 = 0007 No. of SEND words |
DM0001 = 0001 NODE Number |
DM0002 = 0101 MRC-SRC |
DM0003 = 0012 No. of BYTES being sent |
DM0004 = C000 VARIABLE TYPE +1/2 ADDRESS |
DM0005 = 0000 1/2 ADDRESS + 00 |
DM0006 = 0001 No. of ELEMENTS |
Response |
DM0010 = 0004 No. of RECEIVED words |
DM0011 = 0000 RESPONSE CODE |
DM0012 = **** Lower 4 digits in HEX |
DM0013 = **** Upper 4 digits in HEX |
|
5. Change Set Value |
DM0000 = 0009 No. of SEND words |
DM0001 = 0001 NODE Number |
DM0002 = 0102 MRC-SRC |
DM0003 = 0020 No. of BYTES being sent |
DM0004 = C100 VARIABLE TYPE +1/2 ADDRESS |
DM0005 = 0300 1/2 ADDRESS + 00 |
DM0006 = 0001 No. of ELEMENTS |
DM0007 = 0000(HEX) Upper 4 digits of SV |
DM0008 = 00FF(HEX) Lower 4 digits of SV (eg 255) |
Response |
DM0010 = 0004 No. of RECEIVED words |
DM0011 = 0000 RESPONSE CODE |
DM0012 = **** First 16 Bits |
DM0013 = **** Second 16 Bits |
|