This tutorial is intended as a supplement to the original manuals for the products. Therefore, use this as a means to familiarise yourself with the product, and not as a guide for a complete installation. The information in the tutorial is taken from the manual (s):
Downloading a program to NS via CS/CJ PLC
It is possible to transfer a program to the NS-screen via the communication ports of the PLC.
- Start up CX-Programmer, Work Online and go into the Settings for the serial ports.
- If you're connecting the NS to a CS1/CJ1 PLC Peripheral port, use cable NT-CN221 and set the Peripheral port on the PLC for NT Link 1: N 115200k and also set DIP switch SW4 = ON. If you're connecting the NS a CS1/CJ1/CJ2 PLC Hostlink(RS232) port, use cable XW2Z-200T and set the Hostlink port on the PLC for NT Link 1: N 115200k and also set SW5 = OFF.
- Go into the system menu on the NS and set 1: N NTLink High Speed port A or B as appropriate.
- Select Transfer in NS-Designer and Comms. Method