I Am Unable To Set Max Frequency Higher Than 150 Hz In My F7 Inverter.

As default, F7-inverters are set for Heavy Duty (parameter C6-01 = 0) wich means that max frequency is limited to 150 Hz.

If Normal Duty 1 or 2 is selected (C6-01=1 or 2) the setting range will be 0.0 to 400.0 Hz.
 