Can I connect a CJ1 Series PLC to a CS1 expansion rack? - CX-Programmer
Although not mentioned in the CJ1 catalogue, the Interface Control Document for the CJ1 series states:
Section 3.12.2. Requirements of I/O Table Operation I/O Table shall show the unit profile information even if the CPU's unit profile table includes come CS1 series units. This means that a CJ1 PLC can be connected to a CS1 expansion rack. This vastly extends the capability of the CJ1 series. The following conditions also apply when a CS1 expansion rack is used: A CJ1 CPU rack + CS1 I/O base with no empty slot on right side works. A CJ1 CPU rack + CS1 I/O base with an empty slot on left side causes an I/O setting error.