Quick Start Guide For Configuring NX-EIC202 With Rockwell Automation 1 IntroductionThis document shows the basic steps for configuration of a Rockwell Automation PLC to connect to the OMRON NX-EIC202 Ethernet/IP coupler. The guide will assume the hardware installation has already been completed following [1].
This document has been made using the Allen-Bradley 1769-L23E-QB1 Controller, but will apply to other Rockwell based controllers as well. The following is required:
Please be sure to read the related manuals to use the NX-EIC202 Unit safely and properly.
Use the following procedure to prepare the Unit for use. Refer to the reference sections for details on the indicated steps. 2.1 [RSLogix] Install EDS FileFollow the steps below to install (a new version of) an EDS file within RSLogix5000. Both installation as de-installation of the EDS file is done by the EDS Hardware Installation Tool (Tools menu).
2.2 Setting the NX-EIC202 IP AddressPerform the following steps to change the IP address of the Unit in the Rockwell default range (192.168.1.x).
After a power toggle, the new IP address will be active in the Unit. Please find additional information about setting IP address in [1], section 9-4. 2.3 [Sysmac Studio] Setting up the Slave TerminalThe NX-EIC202 Operation Manual (see [1]) describes the procedure to configure the Slave Terminal (NX-EIC202 and the individual NX Units).
After the NX Configuration is finished, please use the following steps to check the resulting I/O Allocation size of the Coupler.
The input and output tag sizes are necessary to configure the Ethernet/IP connection in RSLogix. 2.4 [RSLogix] Configure EIP connectionThe main view of the RSLogix 5000 software provides the way to add the NX-EIC202 to the PLC’s network. Please see below an example of the main view of the tool. Perform the following steps to add the NX-EIC202 to the network.
The NX-EIC202 has now been configured. Please follow the standard procedure of the Rockwell software to download configure the PLC and the network. 3. NX-EIC202 OperationThe Controller Tags shows the Input and Output data allocated to the NX-EIC202. These tags can be used in the PLC program to use the IO data of the coupler.
|
Setting | Class (hex) | Instance (hex) | Attribute (hex) | Example value |
NT server IP address | F5 | 01 | 64 | "192.168.1.119" |
Timezone | F5 | 01 | 66 | (GMT + 09:00) Japan |
Set the following value for the Timezone setting.
Value | Description | Value | Description |
0 | (GMT -12:00) Kwajalein | 22 | (GMT +04:30) Afghanistan |
1 | (GMT -11:00) Midway Island | 23 | (GMT +05:00) Russia ( Yekaterinburg, Perm ) |
2 | (GMT -10:00) USA ( Hawaii ) | 24 | (GMT +05:30) India |
3 | (GMT -09:00) USA ( Alaska ) | 25 | (GMT +05:45) Nepal |
4 | (GMT -08:00) Canada, USA ( Pacific ) | 26 | (GMT +06:00) Russia ( Novosibirsk, Omsk ) |
5 | (GMT -07:00) Canada, USA ( Mountain ) | 27 | (GMT +06:30) Myanmar |
6 | (GMT -06:00) Canada, USA ( Central ) | 28 | (GMT +07:00) Thailand |
7 | (GMT -05:00) Canada, USA ( Eastern ) | 29 | (GMT +07:00) Vietnam |
8 | (GMT -04:00) Canada ( Atlantic ) | 30 | (GMT +08:00) Australia ( Western ) |
9 | (GMT -03:30) Canada ( Newfoundland ) | 31 | (GMT +08:00) China |
10 | (GMT -03:00) Argentina | 32 | (GMT +08:00) Taiwan |
11 | (GMT -02:00) Antarctica | 33 | (GMT +09:00) Japan |
12 | (GMT -01:00) Azores | 34 | (GMT +09:00) Republic of Korea |
13 | (GMT +00:00) England | 35 | (GMT +09:30) Australia ( Northern Territory ), Australia ( South ) |
14 | (GMT +00:00) United Kingdom, Portugal | 36 | (GMT +10:00) Australia ( New South Wales/Queensland/Victoria ) |
15 | (GMT +00:00) Greenwich Mean Time ( UTC ) | 37 | (GMT +10:30) Australia ( Lord Howe Island ) |
16 | (GMT +01:00) France, Germany, Italy, Spain, Switzerland | 38 | (GMT +11:00) New Caledonia |
17 | (GMT +01:00) Sweden | 39 | (GMT +11:30) Norfolk Island |
18 | (GMT +02:00) Bulgaria, Finland, Greece | 40 | (GMT +12:00) New Zealand |
19 | (GMT +03:00) Russia ( Moscow, St.Petersburg ) | 41 | (GMT +12:45) Chatham Island |
20 | (GMT +03:30) Iran | 42 | (GMT +13:00) Tonga |
21 | (GMT +04:00) Russia ( Samara, Izhevsk ) |
Please note a power cycle is required after changing the settings of these parameters.
Any tool or unit which supports CIP messaging can set the NTP setting based on the description above.
The following section shows how to use the Network Configurator tool to download the settings.
Setting NTP server connection using Network Configurator
Perform the following steps of the Operation Manual to configure the Unit using EDS file (see [1] section 9-5).
- Start the Network Configurator
- Register the devices that will participate in the tag data links by dragging the devices from the Hardware List and dropping them in the Network Configuration Pane on the right. Please only add the NX-EIC202.
- Right-click the registered device’s icon to display the pop-up menu, and select Change Node Address. Set the node address of the NX-EIC202 you want to configure.
- Right-click the registered device’s icon to display the pop-up menu, and select Parameter ~ Edit.
- Set the two NTP parameters to the required values. Click OK to close the window.
- Download the updated settings to the coupler. Right-click the registered device’s icon to display the pop-up menu, and select Parameter ~ Download.