Why Is My Ladder Power flow Shown In Yellow? - Sysmac Studio IntroductionWhen online in Sysmac Studio, the ladder power flow is normally shown in green but sometimes the power flow is shown in yellow as shown below:
![]() There is more that one reason for this. Check each of the possibilities below to confirm which is applicable to you.
Reason 1: Program has not be transferred to the controller.If the program has not yet been transferred to the controller, or the program is different to that in the controller then the power flow cannot be monitored.
Solution: Click
Synchronise to validate the program differences, and to transfer the program so that computer and controller are the same.Reason2: The Program has not been assigned to a Task, or is in a Task that is not runningThe program must be assigned to a task, and the task be running in order to monitor the power flow.
Solution: Click
Task Settings->Program Assignment Settings to check the program is assigned to a task. When online click Task Settings->Task Execution Status Monitor to check the task is currently running.Reason 3: The Program has a non-fatal runtime error which is preventing monitoringAny program execution errors during runtime are detected, and the Instruction Error Flag
P_PRGER is set. Examples of such execution errors are:
When execution errors are detected, ENO outputs of PLC instructions and power flow outputs of user created Functions and Function Blocks change to FALSE and power flow cannot be monitored.
Solution: To re-enable monitoring, clear the cause of the error condition and reset the P_PRGER flag
For more details see manual W501-E1-02 NJ-series CPU Unit Software User’s Manual Section 6.6.3 Operation for Instruction Errors
Reason 4: Monitoring of Execution Status is not possibleIn the following cases monitoring the power flow is not possible so power flow is shown in yellow:
For more details see manual W504-E1-10 Sysmac Studio Version 1 Operation Manual Section 7-2-1 Monitoring Link: |