How To Connect NS to PLC Via Dedicated Line IntroductionThis tutorial is designed to cover the NS to PLC connection via a dedicated line using a Gener modem.
I. Setting modems 1. AT & F Recall factory configuration 2. AT + MS: V34 + Mod 11,0,0,19200,19200 without self-adaptation limited to 19200 3. AT% E3 Renegotiation line (bad quality) A 4. AT & D0 DTR signal strength 5. AT! RS: 19200, E, 7.2 format 19,200 bps, even parity, 7 bits, 2 stop 6. Remove ATE0Q1 echo and accounts 7. Turn switch 3 to ON on 2 modems 8. Turn switch 1 to ON on one of the modems (respondent) II. Setting the PLC CS / CJ 1. Configure the custom port of RS232C PLC to Hostlink 19200,7,2, E 2. Switch switch 5 on the front of the PLC OFF
IV. Wiring PLC / NS and Modem Attention!: Be careful to identify both the PLC side and the side of the modem cable Link: |