The following two causes may be the problem.
- The maximum counting speed setting is set to high-speed response and the Counter may be receiving relay chattering, bouncing, or noise input.
Countermeasure:
Set the maximum counting speed to as lower speed. - If the Counter has a prescaling function, the prescale value may be set.
Countermeasure:
Check whether the prescale value is set.