What Is The Relationship Between The Counter's Maximum Counting Speed And Minimum Signal Width?


Maximum Counting Speed (Hz) 30 1K 5K 10K
Minimum Signal Width (ms) 16.7 0.5 0.1 0.05


Example: 30 Hz

Indicates 30 pulses per second (1,000 ms).
Therefore,
1000 ÷ 30 = Approx. 33.3 ms
33 ÷ 2 = 16.7 ms (minimum ON signal width and OFF signal width)

Description
ON/OFF Ratio
Ratio of the count input signal's ON time to OFF time.
(The Counter's maximum counting speed is specified at an ON/OFF ratio of 1:1.)
 