What Is A Substitute Product For MKF-P Flicker Relays?


1.H3CR-A Solid-sate Timers. 8-pin H3CR-A8 cannot be used because they do not support a flicker OFF start, which is the operating mode of MKF-P.
Therefore 11-pin P2CF-11 Surface Mounting Sockets are required, as well as new wiring. Interconnect terminals 2 and 6. Use a power-ON start in mode B, with a flicker OFF start.

2.By setting equivalent ON and OFF times for H3CR-F8 Twin Timers with flicker OFF start, the functionality can be replicated.
It is recommended that the socket is changed to P2CF-08. If you continue to use 8PF(A) Sockets, they must be used with Y92F-42 Adaptors.
The terminal arrangements of external connectors are not compatible.

3.General Comparison of MKF-P and H3CR

Compared item MKF-P H3CR
External connections 8-pin Socket H3CR-A: 11-pin socket
H3CR-F8: 8-pin socket
Supply voltage 24, 50 VAC 50/60 Hz
100/110 VAC 50/60 Hz
200/220 VAC 50/60 Hz
12, 24, 48, 100/110 VDC
H3CR-A:
100 to 240 VAC/100 to 125 VDC
24 to 48 VAC/12 to 48 VDC
H3CR-F8:
100 to 240 VAC, 24 VAC/VDC
12, 48 to 125 VDC
Time range 2 settings fixed at 0.5 and 1.0 s
Special setting fixed at 0.3 s or 1.5 s
Variable setting from 0.05 s with 1 timer
Ficker start OFF start only H3CR-A: ON start or OFF start
H3CR-F8: OFF start only