Industrial Automation
Industrial Automation | Europe

myKnowledge

Main > Product Type > Switching Components
Minimize Text   Default    Enlarge Text
 

Print
E-mail

I'm Using General-Purpose 61F Floatless Level Controllers With Cable Conductor Of 2 mm2 And A Length That Is Less Than 1 km, But It Malfunctions. Is There A Solution For This?


It's possible that the cable conductor diameter is too large. Try changing to 0.75-mm2 conductor, or replace 61F with a long-distance model.

*Stray capacitance increases with thick cable diameters, which shortens the applicable cable length.
 




Comments (View All Comments / Add Comment)

Related Articles
No related articles found.
Created 2009-01-05
Modified 2009-01-05
Views 1903

 