- Personal Computer Ethernet setting by IP Address and Subnet Mask.
- Ethernet Unit: IP Address, Node No., Unit No.
- CX-Programmer and CS1 Programmable Controller is connected with Tool bus Cable.
- CX-Programmer I/O table Window: Unit Setting (CPU bus unit System Setting) is required to be set for Ethernet [IP Address Conversion] by Automatic generation, [Sub net mask] is set.
- 5. CX-Programmer (CX-Net): FINS Local Routing table is created and transferred to CS1.
- 6. Personal Computer issues PING Command to check if Ethernet connection is OK.
- 7. CX-Programmer Communication Setting
1) Personal Computer Model Change / [Network Type] is set [Ethernet].
2) Click [Setting], set FINS destination address [Network] / [Node]
(Node = Ethernet Unit Node Number, Network = Network address set in Routing table)
3) Check Automatic generation method at [Driver] tab / Workstation node Address. Port Number = 9600.