What Is Required For The DRV X-Y Connector XSOUT Signal (SEN Signal), And What Timing Is Required When I Have Have C200H-MC221 Motion Control Units Connected To A Servo Driver From Another Company?


The XSOUT signal (SEN signal) is used to load the present motor position when connecting OMRON Drivers that support absolute values (R88).

(By using Motion Controllers with OMRON Servo Drivers/Servomotors, an absolute system that does not need to search for the origin can be easily constructed.)

Therefore, the XSOUT signal (SEN signal) is not required when connecting servo drivers from another company. As for the timing, the SEN signal will turn ON when Motion Control Units power supplies are turned ON (i.e., when power supplies for PLCs are turned ON). The SEN signal will turn OFF when Servomotors are locked.

 


 