Industrial Automation
Industrial Automation | Europe

myKnowledge

Main > Product Type > Automation Systems > PLCs
Minimize Text   Default    Enlarge Text
 

Print
E-mail

With The CX-Programmer FA Integrated Tool Package, What Is The Procedure To Transfer A Program To A C200HX/HG/HE-Z PLC Or C200HS PLC Memory Cassette? What Is The Procedure To Verify The Data?


The procedure to write data to a Memory Cassette and perform verification is as follows.

  • Set SW1 on the Memory Cassette to OFF (write-enabled) before turning ON power supplies to the C200HX.
  • Turn ON power supplies to C200HX and then connect online.
  • Set the operating mode of the CX-Programmer to PROGRAM Mode.
    Select "View" - "Window" - "Watch Window", right-click in the Watch Window, and select "Add" from the menu.
    Set the address to A270.00.
    Right-click the PLC's name (New PLC 1) displayed in the Watch Window, and select Set from Set/Reset in the menu.
  • To verify the data, set the address to A270.02, right click on the PLC's name (New PLC 1) displayed in the Watch Window, and select Set from Set/Reset in the menu.
  • To check the verification result, set the address to A270.03 and check the value.
    The verification result is stored in A270.03 in the following manner.
    1: Memory Cassette data and user memory data are different.
    Or verification is not possible because CPU Unit is not in PROGRAM mode.
    0: Memory Cassette data and user memory data are the same.


 

 




Comments (View All Comments / Add Comment)

Related Articles
No related articles found.
Created 2008-10-30
Modified 2009-04-30
Views 2674

 

You are not logged in.