What Baudrates And Data Formats Are Handled By Auto Online And In What Order?


The order for searching major settings is as follows:
1st connection was the previous format and then the following order will be used. 

BPS

Protocol

Parity

Data

Stop bit

Model

19.2K

Toolbus

None

8

1

CS/CJ

9600

SYSWAY

Even

7

2

CS/CJ

9600

Toolbus

Odd

8

1

CV

9600

SYSWAY

Even

7

2

C

9600

SYSWAY

Even

7

2

CV

9600

Toolbus

Even

7

2

C

9600

Toolbus

None

8

1

CS/CJ

19.2K

SYSWAY

Even

7

2

CS/CJ

19.2K

Toolbus

Odd

8

1

CV

19.2K

SYSWAY

Even

7

2

C

19.2K

SYSWAY

Even

7

2

CV

19.2K

Toolbus

Even

7

2

C

38.4K

Toolbus

None

8

1

CS/CJ

38.4K

SYSWAY

Even

7

2

CS/CJ

115.2K

Toolbus

None

8

1

CS/CJ

115.2K

SYSWAY

Even

7

2

CS/CJ


 




 



 