Industrial Automation
Industrial Automation | Europe

myKnowledge

Main > Product Type > Software > Configuration
Minimize Text   Default    Enlarge Text
 

Print
E-mail

Why Do I Have A Problem Communicating With NS After Upgrading From CX-One 1.0 To Cx-One 1.1?


There is an identified problem with upgrading CX One V1.0 to V1.1 when using Version up CD.
After updating, when selecting Serial port in CX Designer for communications, you get an error message like : Failed to process CX Server (04) , (060D)
Failed to process CX Server (05) , (0011)
1) Put the update CD in your CD player.
Run setup.exe of \CX-Server\Drivers\CS1\ of the CD.
Uninstallation of CS1 driver is executed.
After finishing it, run setup.exe of \CX-Server\Drivers\CS1\ of the CD again.
Installation of CS1 driver is executed.
After finishing 5), you should be able to access NS-V1 with CX-Designer.
 




Comments (View All Comments / Add Comment)

Related Articles
No related articles found.
Created 2008-10-22
Modified 2009-04-30
Views 3611

 