Vendor |
Server Name |
Product Version |
Result |
4CE Industry |
OPCSysDiag |
1.0 |
Pass |
4CE Industry |
Modbus Server |
2.0.4 |
Pass |
Alstom Technology |
FBSOPC |
1.30a |
Pass (although noted not OPC compliant) |
Amersham Biosciences |
UNICORN |
Zappa build 313 |
Pass |
Applicom International |
applicom IO |
2.1 (reported as 2.1 (1000)) |
Pass |
AXEDA Systems |
OPC DA Server |
1.0.0.2 |
Pass |
CimQuest |
OPC Server for Allen Bradley |
2.25.00.01 (reported as 2.25 (1)) |
Pass |
CimQuest |
OPC Server for Omron |
2.25.00.01 |
Pass |
Cyberlogic Technologies, Inc. |
MBX OPC Server |
5.00.02 |
Pass (although noted not OPC compliant) |
KEPware |
KEPServerEX |
4.12.135 |
Pass |
KW Software GmbH |
KW Software-ProConOS OPC Server |
2.0 |
Pass |
ICONICS Inc |
Modbus OPC Server |
3.07 |
Pass |
ICONICS Inc |
DataStore OPC Server 3.10 |
3.10 |
Pass |
INAT GmbH |
INAT OPC-Server TCPIPH1 S5 and S7 |
2.05.37 |
Pass |
INAT GmbH |
OPC-Server MPI/PPI |
2.05.37 |
Pass |
Invensys Systems / Wonderware |
DASS7 |
1.1 |
Pass |
Matrikon |
OPC Server for Simulation & Test |
1.1.3.230 |
Pass |
National Instruments |
|
4.5.3 (beta) |
Pass |
Northern Dynamic |
OPC Server Toolkit |
2.01 |
Pass |
OSI Software Inc |
OPC Data Access & Historical Data Access Server for the PI System |
1.0.0.14 |
Pass (although noted not OPC compliant) |
Phoenix Contact GmbH & Co. KG |
Interbus OPC Server |
2.12 |
Pass |
Rockwell Software |
RSLinx |
2.30.00 (beta) |
Pass |
SMAR |
OPC & Conf. Server for DFI302 |
3.3.0.0 |
Pass |
SST |
DH+OPC Server |
1.6.16 |
Pass |
SST |
ControlNet OPC Server |
1.3.0 |
Pass |
Siemens AG |
WinCC |
5.0 |
Pass |
Siemens AG |
Simatic WinCC |
V6.0 SP2 Beta |
Pass (although noted not OPC compliant) |
Siemens AG |
Simatic Net OPC Servers |
6.1 |
Pass |
Siemens AG |
IndustrialDataBridge |
6.0.3007 |
Pass |
Siemens |
APACS+OPC Device Server |
1.00 K (beta) |
Pass |
Triconex Corp. |
TS1131 |
3.1 |
Pass |
Wonderware |
InControl |
7.11.1614 |
Pass |
Wonderware |
Virtual PLC Server |
1.0 (beta) |
Pass |
The following products have not passed:
Vendor |
Server Name |
Product Version |
Comment |
Klinkmann |
Omron driver |
? |
Ignores ‘Read from Device’ option. Seen to lose device values, potential control risk. |
OPC Labs |
Time Monitor |
2.01 |
Fail. Group inactive, item active still results in a callback |
Rockwell Software |
RSView32 |
6.2 |
V1.0a Server only – not supported |
Siemens AG |
WinCC |
4.1 |
V1.0a Server only – not supported. Contact Siemens to upgrade to V5.0 |
Siemens Building Technologies Inc |
MK8000 MP1.30 |
MP1.30 |
Could not get the simplest of operations to succeed |
Softing |
OPC Toolkit |
? |
Some support issues reported |
USDATA Corp |
Factorylink |
7.0.1 (beta) |
Single test failed to connect. |