What Is The Difference Between The CONDITION ON Instruction (UP) For The CS/CJ-Series PLCs, And DIFU Instruction?




Both the CONDITION ON (UP) and CONDITION OFF (DOWN) instructions were added with the introduction of the CS/CJ-Series, but here we will explain only the CONDITION ON (UP) Instruction.
CONDITION ON Instruction (UP) Operation Specifications

When the execution condition to UP turns ON, the execution condition output from UP will turn ON for 1 cycle.

Differences between CONDITION ON Instruction (UP) and Other Differentiated Instructions

The differences between --|↑|--, the DIFU instruction, and the CONDITION ON instruction (UP) are given in Table 1.



Program Operation
1.When the Device A Run Time (D201) reaches the Device A Time for Lubrication (CIO 1), the CONDITION ON instruction (UP) causes the execution condition to turn ON for one scan, which will turn ON the Device A Reached Time for Lubrication Bit (CIO 2.00) will turn ON. The self-holding bit (CIO 2.00) will cause the warning bit to remain ON.

2.When the Alarm Stop Pushbutton Bit (CIO. 0.01) turns ON, the self-holding bit will be reset, and the alarm output bit (CIO 2.00) will turn OFF.
Reference:
We have explained the CONDITION ON instruction (UP) here. The CONDITION OFF instruction (DOWN) is different only in that, when the input signal turns OFF, the execution condition will turn ON for one cycle. The other characteristics of the CONDITION OFF instruction (DOWN) are the same as those of the CONDITION ON instruction (UP).

 

 




Comments (View All Comments / Add Comment)

Related Articles
How Do I Write A Program To Delay Turning ON A Work Bit For 1 Scan After An Input A Turns ON And Keep The Work Bit ON For Only 1 Scan When Using A CS/CJ-Series PLC?
As shown in Figure 1, the program delays for 1 scan after input A turns ON, and turns ON work bit W2.00 for only 1 scan, as shown in Figure 2.   Operation:...
What Outputs Turn OFF With In Interlocked Program Sections Interlock Instruction (IL/ILC) And What Ones Don't?
Introduction The Interlock Instructions can be used to turn OFF all the sequence outputs from a specific program block, as might be necessary to process an emergency stop...
The Address Does Not Update Correctly With IR1 In A Program Using The Index Register As Shown In Figure 1. Why?
Ladder Program Operation Specifications Before explaining the problems with the ladder program, we will explain the system operation specifications. *When one of...
 
Created 2008-10-31
Modified 2009-04-29
Views 456

 

You are not logged in.