Industrial Automation
Industrial Automation | Europe

What is myOMRON?

Click here to find out

Search myKnowledge

Login

Username

Password



Register / Forgot password?

myKnowledge

Main > Product Type > Control Components
Minimize Text   Default    Enlarge Text
 

Print
E-mail

Why Is TC Output OFF While SV Is Above PV?


Introduction

When you turn on the power for the first time after you purchase an E5_N Temperature Controller, and set the control method into PID as well as change the SP, The self-tuning (ST) will start. If the external heater is OFF at this time, the E5_N determines that the PID calculation is not properly processed, and shifts to the limit cycle tuning method. In limit cycle tuning, the outputs are forced to turn on and off to determine the PID by analyzing the temperature (PV) change.

Explanation

Due to ambient air and the heat of surrounding machines, the temperature of the to-be-measured-PV goes up. This makes the E5_N shift to the limit cycle. It turns the outputs OFF and waits for the temperature decline. However, the temperature remains high due to above (external) factors, and the outputs are kept OFF even when the SP is then set to 130℃. In this situation, the temperature of the control target whose temperature is measured does not rise even the external heater is on.

When you use ST (selftuning), be sure to turn on the power on the load which is connected to the control output before or at the same time when temperature controller starts operation. See the extract from the Users Manual in below:

self tuning

 

 




Comments (View All Comments / Add Comment)

Related Articles
Connecting E5_N Series to CPM2C-CIF21
Introduction This note describes a simple way of connecting Omron CPM2C-CIF21 communication unit to E5_N temperature controllers to read PV and Status and write the...
We Need To Start A Fan When The Temperature Rises And Stop It When The Temperature Drops.
Set cooling control (direct operation). Change the direct/reverse operation setting to direct operation. For example, if you set the temperature (e.g., to 30...
When Can The Manual Reset Be Used For E5[]N/E5[]K Temperature Controllers?
The manual reset can be used for P or PD control. There is an offset for the set point when using P or PD control because there is no integral control action. There is...
 
Created 2010-06-01
Modified 2010-06-03
Views 170

 

You are not logged in.